Troubleshooting the datasite configured panel – Rockwell Automation 1748 DataSite Configured Panel Installation Instructions User Manual
Page 34
 
Publication 1748-IN001B-EN-P - May 2009
34 Troubleshooting
Troubleshooting the 
DataSite Configured Panel
The following table covers a brief technical approach to verifying the 
functionality of the following components:
•
DataSite controller
•
Human-machine interface (HMI)
•
Transmit radio
•
Batteries
•
Solar charge controller
It is recommended that troubleshooting of the DataSite configured panel 
begin with the use of the following troubleshooting table for a more systematic 
and modular approach. The numbers in parentheses ( ) refer to the 
components as shown on 
For troubleshooting information on the DataSite controller or its associated 
software, refer to the related publications listed in the table, 
Related publications for DataSite configured panel on page 5
If additional information on the DataSite configured panel operation is 
needed, contact Rockwell Automation Technical Support. 
Troubleshooting the DataSite Configured Panel
Problem
Component
Possible Cause
Check
Action
No power at the 
DataSite controller 
(1)
Wire
Wire fault
Make sure that all connections 
are tight and that there is 
continuity in the wires.
If the wire is faulty, tighten the terminal 
or replace the wire as necessary.
Fuse
Fuse blown
Check to see that the fuse has 
not opened.
Replace the fuse if it is open.
Batteries
No charge in 
battery
Perform load test
(1)
to confirm the
condition of the battery.
If battery test fails, replace battery with 
Rockwell approved replacement part.
Battery terminal
Corrosion on 
Terminal
Check if the integrity of the 
battery terminal has been 
compromised, and if there are 
loose or corroded terminals
If compromised, replace battery with 
Rockwell approved replacement part.
Solar controller
Short in solar 
panel
If there is light reaching the solar 
panel, disconnect the solar panel 
from the controller and ensure 
that there is voltage at the solar 
panel terminals.
If no voltage is present, ensure that 
there is not a short at the solar panel or 
a bad connection at the solar panel 
junction box. Replace the solar panel if 
there is no voltage at the panel output.
Shorted battery
If there is light reaching the solar 
panel and there is voltage at the 
solar panel terminals, ensure that 
the battery output terminals read 
11.5V or greater.
If the reading is lower than 11.5V, the 
battery may be shorted or possibly 
deep-cycled. Charge the battery, and 
then recheck the system. If necessary, 
replace the battery.
Shorted solar 
controller
Check the solar panel and 
battery.
If after checking the solar panel and 
battery, the charge light still does not 
illuminate, contact Rockwell 
Automation Technical Support.