46 DataSite Configured Panel Battery

Charging and Discharging

The batteries supplied with the DataSite configured panel are designed for
discharge in temperatures ranging from -40 °C to 60 °C (-40 °F to 140 °F) and
to be charged in temperatures ranging from -20 °C to 50 °C (-4 °F to 122 °F).
Charging or discharging of these batteries outside of the specified ranges can
cause reduced battery life.

Operating Temperature

When installing the DataSite configured panel in regions where the ambient
temperature could fall below 16 °C (60.8 °F), derating the DataSite configured
panel backup time is necessary to ensure reliable use of the system. The battery
capacity of the DataSite configured panel should be derated as the temperature
decreases.

See the table,

DataSite Configured Panel Battery Derating

, for derated hours

of backup based on ambient temperature. This table assumes the battery can
be charged to 100% capacity. For details on battery capacity, see

Recommended Battery Replacement Schedule on page 31

.

DataSite Configured Panel Battery Derating

Average summer
temperature

Maximum duration without sunlight

14 Ah battery

28 Ah battery

56 Ah battery

-40 °C (-40 °F)

8 hours

16 hours

32 hours

-30 °C (-22 °F)

11 hours

22 hours

45 hours

-20 °C (-4 °F)

14 hours

28 hours

57 hours

-10 °C (14 °F)

18 hours

36 hours

72 hours

0 °C (32 °F)

21 hours

42 hours

84 hours

10 °C (50 °F)

23 hours

46 hours

92 hours

20 °C (68 °F)

24 hours

48 hours

97 hours

30 °C (86 °F)

25 hours

50 hours

101 hours

40 °C (104 °F)

25 hours

51 hours

103 hours

50 °C (122 °F)

26 hours

52 hours

105 hours

60 °C (140 °F)

26 hours

52 hours

105 hours

70 °C (158 °F)

26 hours

52 hours

105 hours