Set the network address, Use the rockwell bootp/dhcp utility – Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 29

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

Configure the Module for Your EtherNet/IP Network 21

Set the Network Address

The I/O block ships with the rotary switches set to 999 and DHCP enabled.
To change the network address, you can do one of the following:

1. Adjust the switches on the front of the module.

2. Use a Dynamic Host Configuration Protocol (DHCP) server, such as

Rockwell Automation BootP/DHCP.

3. Retrieve the IP address from nonvolatile memory.

The I/O block reads the switches first to determine if the switches are set to a
valid number. Set the network address by adjusting the 3 switches on the front
of the module. Use a small blade screwdriver to rotate the switches. Line up
the small notch on the switch with the number setting you wish to use. Valid
settings range from 001…254.

Network Address Example

When the switches are set to a valid number, the I/O block’s IP address is
192.168.1.xxx (where xxx represents the number set on the switches). The I/O
block’s subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0.
When the I/O block uses the network address set on the switches, the I/O
block does not have a host name assigned to it or use any Domain Name
Server.

If the switches are set to an invalid number (for example, 000 or a value greater
than 254, excluding 888), the I/O block checks to see if DHCP is enabled. If
DHCP is enabled, the I/O block asks for an address from a DHCP server.
The DHCP server also assigns other Transport Control Protocol (TCP)
parameters.

If DHCP is not enabled, and the switches are set to an invalid number, the
I/O block uses the IP address (along with other TCP configurable parameters)
stored in nonvolatile memory.

Use the Rockwell
BootP/DHCP Utility

The Rockwell BootP/DHCP utility is a stand alone program that incorporates
the functionality of standard BootP/DHCP software with a user-friendly
graphical interface. It is located in the Utils directory on the RSLogix 5000

This example
shows the network
address set at 163

44233

Advertising