Chapter summary and what’s next – Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 78

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

70 Interpret Status Indicators

Chapter Summary and
What’s Next

In this chapter, you read how to interpret the Status Indicators on the module.
The next chapter describes how to troubleshoot the module using
RSLogix 5000.

Network status Off

The device is not initialized or the module does not
have an IP address.

Flashing green

The device has an IP address, but no CIP
connections are established.

Green

The device is online, has an IP address, and CIP
connections are established.

Flashing red

One or more connections have timed out.

Red

The module has detected that its IP address is
already in use.

Network link
status

Off

No link established.

Green

Link established on indicated port at 100 Mbps.

Flashing green

Link activity present on indicated port at 100 Mbps.

Yellow

Link established on indicated port at 10 Mbps.

Flashing yellow

Link activity present on indicated port at 10 Mbps.

Auxiliary status Off

No power to device or input not valid.

Green

Power applied to device.

Digital input
status

Off

No valid input.

Yellow

Valid input.

Red

Sensor source voltage shorted.

Flashing red

Sensor source open wire.

IMPORTANT

The Module Status Indicator will flash red and green for a
maximum of 30 seconds while the module completes its POST
(Power-On Self Test).

Indicator Status for Module

Status

Description