Input tags – Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 87

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

Module Tags 79

Input Tags

The following table describes the input tags generated in RSLogix 5000.

C.CaptureOffOn.x

INT

Enables capturing OFF to ON events on a per point basis. If disabled (0), that point will not
record timestamp data for OFF to ON input transitions.

0 = Capture disabled for OFF to ON input transitions
1 = Capture enabled (default) for OFF to ON input transitions

This option is useful if you want to avoid reporting data on the module for events in which
you have no interest.

C.CaptureOnOff.x

INT

Enables capturing ON to OFF events on a per point basis. If disabled (0), that point will not
record timestamp data for ON to OFF input transitions.

0 = Capture disabled for ON to OFF input transitions
1 = Capture enabled (default) for ON to OFF input transitions

This option is useful if you want to avoid reporting data on the module for events in which
you have no interest.

Configuration Tags

Tag Name

Type

Description

Input Tags

Tag Name

Type

Set on Per
Point or
Modulewide
basis

Description

I.Fault

DINT

Modulewide

Communication fault - The controller sets this tag to 1 for all 32 bits if a
communication fault occurs on the module otherwise all bits are zero.

I.Data

INT

Per point

Status of the input point. This data is filtered if the Input Filter feature is used
on the module. Thus, an input change must pass through the filter before it is
seen in this tag.

0 = input is OFF
1 = input is ON

For example, if input 3 is ON, I.Data.3 = 1.

I.PtXX_YYOpenWire

BOOL

Per point

XX = even numbered input 0…14
YY = odd numbered input 1…15

An OpenWire condition exists per I/O connector. For example, 00_01 or 14_15

0 = no fault
1 = Open Wire

For more information on Open Wire Detection, see

page 45

.