Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 89

Advertising
background image

Publication 1732E-UM002A-EN-P - March 2010

Module Tags 81

I.OffsetTimeStamp

DINT[2]

Modulewide

The time when the PTP message was received to cause the Local Clock Offset
to update.

This value is initially zero. The first timestamp occurs when the module
synchronizes with the Grandmaster clock.

I.GrandMasterClockID

DINT[2]

Modulewide

The I.D. number of the Grandmaster clock that the module is synchronized to.

I.Timestamp[16].OffOn[2] DINT[2]

Per point

Timestamp value with an input’s OFF to ON transition. This tag is a 16 x 2 32-bit
array.

This value is cleared after the data has been acknowledged via the O.EventAck
and O.NewData tags. For more information on clearing timestamp data, see
see

page 64

.

I.Timestamp[16].OnOff[2] DINT[2]

Per point

Timestamp value with an input’s ON to OFF transition. This tag is a 16 x 2 32-bit
array.

This value is cleared after the data has been acknowledged via the O.EventAck
and O.NewData tags. For more information on clearing timestamp data, see

page 64

.

I.SyncedToMaster

BOOL

Modulewide

Indicates if the module is synchronized with a master clock.

1 = Synchronized
0 = Not synchronized

(1)

With the Per point tags, there is one bit per input. For example, bit 0 represents input 0, bit 7 represents input 7 and so on.

Input Tags

Tag Name

Type

Set on Per
Point or
Modulewide
basis

Description