Specifications, Appendix a, Armorblock 2 port ethernet module specifications – Rockwell Automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporting Sequence of Events User Manual

Page 81: Ix a on, Appendix

Advertising
background image

73

Publication 1732E-UM002A-EN-P - March 2010

Appendix

A

ArmorBlock 2 Port Ethernet
Module Specifications

Specifications

ArmorBlock 2 Port Ethernet Module Input Specifications – 1732E-IB16M12SOEDR

Attributes

Value

Number of inputs

16

Input type

Sink, 24V DC

Voltage, off-state input, max

5V DC

Voltage, on-state input, max

30V DC

Voltage, on-state input, nom

24V DC

Voltage, on-state input, min

11V DC

Current, off-state input, max

1.5 mA @ 5V DC

Current, on-state input, max

5 mA @ 30V DC

Voltage, sensor source, max

30V DC

Voltage, sensor source, min

10V DC

Input delay time
ON to OFF
OFF to ON

0…16000

μ

s

Isolation voltage

50V (continuous), Basic Insulation Type, Inputs and Sensor
Power to Network
No isolation between individual Inputs or between
Network channels Type tested at 707V DC for 60s

Voltage, auxiliary power, max

30V DC

Voltage, auxiliary power, min

12V DC

Current, Ethernet system
power, max
(pins 2, 3 sensor
source/module power)

1.2 A

Current, sensor source, per
input, max

50 mA

Current, sensor source, per
connector, max

100 mA

Timestamp accuracy

100

μ

s

Refer to the module input delay tables on

page 68

.

Communication rate

EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment

Advertising