Publication 4100-5.3 - June 1999

Installation & Hook-Up 13

The mounting tabs should be bolted firmly to the metal enclosure.
The following diagram shows the proper method of mounting to
make sure the ALEC is grounded.

Figure 2.1 Proper Mounting and Grounding Method

Connecting the ALEC

Before attempting to use the ALEC, the Mode configuration, AxisLink
Address, and DIP switches on the front panel must be set as required.

ATTENTION

!

To avoid a shock hazard, remove all power to the system
panel before mounting the ALEC.

#10 AWG to
Ground Bus

Ground
Lug

Internal Star Washers

ALEC Mounting Tab

Size 1/4 - 20 or M6
Hardware

Tapped Hole
(Minimum of 3 Threads)

Metal Panel
(Must be connected to
earth ground.)

Scrape paint off panel to insure
electrical connection between
chassis and grounded metal plate.