16 Installation & Hook-Up

Figure 2.3 Wiring the AxisLink Connector

When the ALEC is either the first module or the last module on the
AxisLink cable, an external termination resistor must be installed. If
you are using AxisLink in standard configuration, the resistor should
be 150 Ohms. If you are using Extended AxisLink, the termination
resistor should be 300 Ohms. These are in addition to the internal
resistors set by DIP switches 5 and 6 on the ALEC front panel.

IMPORTANT

Anchor the cable so that no more than 2 feet of cable is
left unsupported. The excessive weight of an unanchored
cable could pull the plug out of the connector.

ATTENTION

!

Install the termination resistor only if your ALEC is
either the first or last module on the AxisLink line.

ATTENTION

!

Even though AxisLink and RIO use the same cable, the
connections are not interchangeable. Do not mix
AxisLink and RIO connections. It causes both systems to
not work properly.

150

*

300

*

1

2

1

2

Blue

Shield

Clear

Black

Shield

Yellow

AxisLink Wiring

Standard Length

Extended Length

Carol C8014
Belden 9182

A-B 1770-CD
Belden 9463

*Install termination resistor only if this is the first or last
module on the AxisLink line.

AxisLink Cable

AxisLink Cable