Upgrading From ALEC Series C to Series D 49

Resetting the Encoder Mode

The following table shows the differences between series C and series
D for setting the switches for the update frequency and the output
voltage for the encoder.

Encoder OK LED

An Encoder OK LED has been added just below the AxisLink
connector. This provides at-a-glance verification that the encoder
signal is being received.

Table B.3 Comparative Switch Settings

Update Rate
Encoder
Output

Setting for ALEC series
C
(Mode Switch)

Setting for ALEC series D
(Mode Switch; DIP Switch
Position)

250Hz

5V

8

0; DIP Switch 1 is Right

250Hz

12V

9

0; DIP Switch 1 is Left

350 Hz

5V

6

2; DIP Switch 1 is Right

350 Hz

12V

7

2; DIP Switch 1 is Left

500Hz

5V

4

4; DIP Switch 1 is Right

500Hz

12V

5

4; DIP Switch 1 is Left

700 Hz

5V

2

5; DIP Switch 1 is Right

700 Hz

12V

3

5; DIP Switch 1 is Left

1000 Hz

5V

0

7; DIP Switch 1 is Right

1000 Hz

12V

1

7; DIP Switch 1 is Left