Rockwell Automation 4100 ALEC AXIS LINK ENCODER CONVERTER User Manual

Page 26

Advertising
background image

Publication 4100-5.3 - June 1999

18 Installation & Hook-Up

all the way to the right for 5V encoders. See the “Setup” chapter in this
manual for information on selecting the encoder voltage.

Allen-Bradley 845F, 845H, and 845T Encoders

If you are using an Allen-Bradley 845F, 845H, or 845T incremental
encoder, use the following table for your connections.

Allen-Bradley 845K Encoders

If you are using an Allen-Bradley 485K-SAxZx4-xxY3 incremental
encoder, use the following table for your connections.

ATTENTION

!

The required mode must be selected before applying
power to the ALEC. Improper voltage applied to the
encoder can cause damage to the encoder, the ALEC, and
to the operator.

Table 2.4 ALEC Connections for AB

845F, 845H, and 845T Encoders

ALEC Signal

4100-CAExx
Wire Color

Encoder Pin

Encoder
Signal

A+
A-

White
Black

A
H

CH-A Output
CH-/A Output

B+
B-

Green
Black

B
I

CH-B Output
Ch-/B Output

Z+
Z-

Blue
Black

C
J

CH-Z Output
CH-/Z Output

Power
Common

Red
Black

D
F

B+ Input
B+ Return

Table 2.5 ALEC Connections for AB 845K Encoders

ALEC Signal

4100-CAExx
Wire Color

Encoder
Wire Color

Encoder
Signal

A+
A-

White
Black

White
Black

CH-A Output
CH-/A Output

B+
B-

Green
Black

Blue
Black

CH-B Output
Ch-/B Output

Z+
Z-

Blue
Black

Green
Black

CH-Z Output
CH-/Z Output