Publication 4100-5.3 - June 1999

32 Setup

The correct mode must be selected before applying power to the
ALEC and before connecting the encoder, otherwise an improper
voltage may be applied to the encoder, possibly causing damage.
Remember, the ALEC only reads the mode switch at power up or after
reset to determine the periodic update rate.

Table 3.3 Alec Modes for Use with Allen-Bradley Encoders

For Allen-Bradley
Encoder Model

Set Mode Switch
to

Set DIP Switch 1
for Encoder
Voltage

845F-SJxZ14-xxYx...
845F-SJxZ24-xxYx...

0 - 7
0 - 7

5V

12V

845H-SJxx14xxyx...
845H-SJxx24xxYx...

0 - 7
0 - 7

5V

12V

845K-SAxZ14-xxY3
845K-SAxZ24-xxY3

0 - 7
0 - 7

5V

12V

845P-SHC14-xx3

0 - 7

5V

845T-xx12Exx...
845T-xx13Exx...
845T-xx42Exx...
845T-xx43Exx...

0 - 7
0 - 7
0 - 7
0 - 7

5V
5V

12V
12V

ATTENTION

!

Select the proper Mode and DIP Switch settings before
applying power to the ALEC to avoid encoder damage.

IMPORTANT

Encoders in a given family not shown in the above table
are NOT compatible with the ALEC and should not be
used.