14

Rockwell Automation Publication 2080-UM001D-EN-E - September 2012

Chapter 2 About Your Controller

Schematic (Using ANSI/CSA Symbols)

Emergency-stop
push button

230V AC

Operation of either of these contacts will

remove power from the external I/O

circuits, stopping machine motion.

Fuse

MCR

Fuse

MCR

MCR

MCR

Stop

Start

Line terminals: Connect to terminals of power supply

Line terminals: Connect to 24V DC terminals of
power supply

230V AC
output
circuits

Disconnect

Isolation
transformer

115V AC or
230V AC
I/O circuits

L1

L2

Master Control Relay (MCR)
Cat. No. 700-PK400A1

Suppressor
Cat. No. 700-N24

(Lo)

(Hi)

DC power supply. Use
NEC Class 2 for UL
Listing

.

X1

X2

115V AC or
230V AC

_

+

MCR

24 V DC
I/O
circuits

Suppr.

Overtravel
limit switch