Appendix A Specifications

Micro800 Programmable Controller External AC Power Supply

General

Attribute

Value

Dimensions, HxWxD

90 x 45 x 80 mm (3.55 x 1.78 x 3.15 in.)

Shipping weight

0.34 kg (0.75 lb)

Supply voltage range

(1)

(1)

Any fluctuation in voltage source must be within 85V...264V. Do not connect the adapter to a power source that has fluctuations
outside of this range.

100V…120V AC, 1 A
200…240V AC, 0.5 A

Supply frequency

47…63 Hz

Supply power

24V DC, 1.6 A

Inrush current, max

24A @ 132V for 10 ms
40A @ 263V for 10 ms

Power consumption
(Output power)

38.4 W @ 100V AC, 38.4 W @ 240V AC

Power dissipation
(Input power)

45.1 W @ 100V AC, 44.0 W @ 240V AC

Isolation voltage

250V (continuous), Primary to Secondary: Reinforced Insulation Type
Type tested for 60s @ 2300V AC primary to secondary and 1480V AC
primary to earth ground.

Output ratings

24V DC, 1.6A, 38.4 W max.

Enclosure type rating

Meets IP20

Wire size

0.32... 2.1 mm² (22...14 AWG) solid copper wire or
0.32... 1.3 mm² (22...16 AWG) stranded copper wire
rated @ 90 °C (194 °F ) insulation max

Terminal screw torque

0.5…0.6 Nm (4.4…5.3 lb-in.)
(using a Phillips-head or 2.5 mm (0.10in.) flat-blade screwdriver)

Wiring category

(2)

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication

1770-4.1

.

2 – on power ports

Insulation stripping length

7 mm (0.28 in.)

North American temp code

T4A