Page 60

52
Rockwell Automation Publication 2080-UM001D-EN-E - September 2012
Appendix A Specifications
Micro800 Programmable Controller External AC Power Supply
General
Attribute
Value
Dimensions, HxWxD
90 x 45 x 80 mm (3.55 x 1.78 x 3.15 in.)
Shipping weight
0.34 kg (0.75 lb)
Supply voltage range
(1)
(1)
Any fluctuation in voltage source must be within 85V...264V. Do not connect the adapter to a power source that has fluctuations
outside of this range.
100V…120V AC, 1 A
200…240V AC, 0.5 A
Supply frequency
47…63 Hz
Supply power
24V DC, 1.6 A
Inrush current, max
24A @ 132V for 10 ms
40A @ 263V for 10 ms
Power consumption
(Output power)
38.4 W @ 100V AC, 38.4 W @ 240V AC
Power dissipation
(Input power)
45.1 W @ 100V AC, 44.0 W @ 240V AC
Isolation voltage
250V (continuous), Primary to Secondary: Reinforced Insulation Type
Type tested for 60s @ 2300V AC primary to secondary and 1480V AC
primary to earth ground.
Output ratings
24V DC, 1.6A, 38.4 W max.
Enclosure type rating
Meets IP20
Wire size
0.32... 2.1 mm² (22...14 AWG) solid copper wire or
0.32... 1.3 mm² (22...16 AWG) stranded copper wire
rated @ 90 °C (194 °F ) insulation max
Terminal screw torque
0.5…0.6 Nm (4.4…5.3 lb-in.)
(using a Phillips-head or 2.5 mm (0.10in.) flat-blade screwdriver)
Wiring category
(2)
(2)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication
.
2 – on power ports
Insulation stripping length
7 mm (0.28 in.)
North American temp code
T4A