Calculating rack size – Rockwell Automation 2705 REDIPANEL KEYPAD MODULE USER MANUAL User Manual

Page 24

Advertising
background image

with PLC Controllers

Chapter 4
Configuring the Bulletin 2705 Keypad Module

4–7

The 2705 Keypad Module can be configured for any of four rack sizes:

1

/

4

,

1

/

2

,

3

/

4

, and a full rack. Rack sizes relate to the amount of I/O accessible to

each rack: 32 I/O bits or points for

1

/

4

rack, 64 for

1

/

2

rack, 96 for

3

/

4

rack

and 128 for a full rack. You set DIP switches for the rack size you want in
your system design. See Chapter 5 on DIP switch settings.

IMPORTANT NOTE: For stored messages, you must configure for

1

/

2

rack or larger. You cannot use stored messages with

1

/

4

rack.

Note: Stored message display requires

3

/

4

rack to use the BCD mode. BCD

mode can only be configured for

1

/

4

or

1

/

2

rack if message storage is

disabled.

Table 4.D shows the functional characteristics of the Keypad Module
configured in the available rack sizes:

Table 4.D
2705 Keypad Module Functions by Rack Size

Stored Message

BCD Mode

Binary or

Integer Mode

(8 Digits)

N mber of

Rack Size

Stored Message

Capability

Number of BCD

Digits

Number of

ASCII

Characters from

PLC

Number of

ASCII

Characters from

PLC

Number of

Destination Bits

1

/

4

Rack

No

6

0

0

0

1

/

2

Rack

BCD=N

Other=Yes

8

2

4

16

3

/

4

Rack

Yes

8

8

8

BCD=32

Others=48

Full Rack

Yes

8

10

12

BCD=64

Others=80

Calculating Rack Size

Advertising