Chapter 7
Programming

7–19

Rungs A, B and C set the program up:

!

+

+

+

BLOCK XFER READ

DATA ADDR:

0030

MODULE ADDR:

111

BLOCK LENGTH

14

FILE:

0200–0215

+

+

+

+

!

!

!

!

!

+

!

!

!

(EN)

011

+

(DN)

+

+

+

BLOCK XFER WRITE

DATA ADDR:

0031

MODULE ADDR:

111

BLOCK LENGTH

14

FILE:

0400–0415

+

+

+

+

!

+

!

!

!

(EN)

011

+

(DN)

!

17

111

17

16

111

16

+

+

FILE TO FILE MOVE

COUNTER ADDR: 0031

POSITION:

014

FILE LENGTH

014

FILE A:

0200–0215

FILE: B: 0300–0315

RATE PER SCAN: 014

+

+

+

+

!

+

!

!

!

!

!

!

!

(EN)

0033

(DN)

17

0033

15

!

!

!

!

!

!
!

!

!

!

!

!

!
!

A

B

+

C

111

17

+

+

The block transfers and the file–to–file move allow for communications from
the sub–scanner to the programmable controller. The block length of 14
allows for 8 utility words needed by the sub–scanner and 6 words (or

3

/

4

rack) for the Keypad Module. The resulting input/output image tables in
Figure 7.9, on the following page, go along with this programming example
for Keypad Module.

Program Set-up