Rockwell Automation 2705 REDIPANEL KEYPAD MODULE USER MANUAL User Manual
Page 46

Chapter 7
Programming
7–8
Figure 7.5
Rung 2:5
11
16
MOV
MOV
16
F2
Function
Key
I:020
] [
Rung 2:6
MOV
Source
I:021
50
Dest
C5:1.PRE
69
MOV
Source
2
Dest
0:022
2
MOV
Source
C5:1.PRE
69
Dest
0:021
69
Enter
Key
I:020
] [
Enter
Key
I:020
] [
MOV
In the example shown in Figure 7.5, rung 2:5 is used to move the value from
the input image table, I:021, to counter C5.1 preset, each time the Enter key
is pressed.
Rung 2:6 in Figure 7.5 shows how the function key F2 or the Enter key are
used to display stored message #2,
”C5.1 PRE.=”
, on the left side of the
keypad and the current or new preset value of counter C5.1 on the right.
This rung is used strictly to allow the operator to view the value that is about
to be changed. To actually change the preset, the new value must first be
entered into the input image table. This is accomplished by first punching in
the desired preset value using the numeric keys on the Keypad Module, then
pressing the ENTER key. The new value is then placed in the input image
table or in the case of this particular configuration, word I:021. Placing rung
2:5 before rung 2:6 ensures the new updated preset value will be displayed.