Figure 5.6 gives the switch functions and settings for Switch Bank #3. These
switch bank #3 settings are for all PLC’s.

Figure 5.5
Setting Switch Bank #2

ON

OFF

ON

OFF

SW–2

ON

OFF

SW–2

Example

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

RACK SIZE

1/4

1–ON

2–ON

1/2

1–ON

2–OFF

3/4

1–OFF

2–ON

Full

1–OFF

2–OFF

STORED MESSAGE

ENABLED

4–OFF

DISABLED

4–ON

SPLIT DISPALY

XT

5–OFF

AT

5–ON

KEYBOARD STYLE *

TRACKING

6–OFF

BCD

6–ON

SMD/DEST FORMAT

SWITCHES 7&8

NOT USED

Rack Size 1/2

NA

Stored message display ENABLED
Split display DISABLED
AT–style keyboard
DEST/SMD/Tracking

DISABLED

3–OFF

ENABLED

3–ON

Figure 5.6
Setting Switch Bank

#3

Enable STORED MESSAGE to be able to store and retrieve messages on the
EEPROM inside the keypad module. If STORED MESSAGE is disabled,
messages can only be retrieved from PLC memory.

Enable SPLIT DISPLAY to control what is displayed during operator entry.
Refer to page 6–4 for more information.

The DEST. and SMD FORMAT controls the numeric format for the
destination word in the input image table and the SMD word in the output
image table.

When BCD is selected the SMD and destination numbers are in BCD
format. When TRACKING is selected these values will follow the data type
set by DIP switches 3 and 4 on switch bank #2.

Note: On Series B Revision D or earlier modules, DIP switch 6 on switch
bank #3 is not used and the format is always BCD.