Chapter 3

Installing Your PanelView Terminal

Installing Your PanelView 1200 Terminal

Chapter 3

3-4

The Remote I/O Connector

The Remote I/O connector at the back of the PanelView 1200 terminal
connects the terminal to the host PLC controller via the Remote I/O link,
as shown in the following figure.

If the PanelView 1200 terminal is the last device on the link, connect a 1/2
watt terminating resistor across pins 1 and 2. The value of the resistor
depends on the Remote I/O baud rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150

W resistor (A-B part

#740018-29)

for 230 kilobaud, use an 82

W resistor (A-B part #740018-23)

Figure 1.4

Remote I/O Connector

20163

2 SHIELD 1

The AC Power Connector

The PanelView 1200 terminal requires 115/230 VAC, 50/60 Hz.

Before connecting the power cable to the terminal, make sure the cable is
not carrying power. Since the PanelView 1200 terminal has no power
switch, connecting the AC power will start the terminal if power is present
in the cable.

Attention Incorrect power wire connection can cause personal
injury or damage to equipment.