Troubleshooting

Appendix B

B-7

Error code

What to do

Probable causes

180

Timed out, 1771 backplane module not

responding"

PLC controller in program mode, or PanelView

1200 terminal in configuration mode.
The PassĆThrough block transfer assignment in

the PanelView 1200 terminal doesn't match the

PassĆThrough block transfer assignment in the

application file being downloaded.

Put the PLC controller and the PanelView 1200

terminal in run mode.
Match the address assignments.

186

ACK timeout"

Remote I/O cables are disconnected.
Noisy line.

The computer's address is the same as the PLC

station address, when using a KT or KT2 device.

Ensure that both ends of the Remote I/O cables

are connected and terminated according to the

baud rate used.
Reassign the KT or KT2 address.

190

All others"

Programming terminal is not connected to Data

Highway Plus network.

Connect programming terminal to Data Highway

Plus network.

208

Error Opening Network"

Wrong KT2 driver card location. The switch

settings on the KT2 card don't match the

settings entered in the PassĆThrough download

configuration.

Ensure that the settings on the KT2 card match

those entered in the PassĆThrough download

configuration.

211

Bad configuration file format"

Trying to download through a PLCĆ5/40 where

the PanelView 1200 terminal is assigned a rack

number greater than 7.
The switch settings on the KT card don't match

the settings entered in the PassĆThrough

download configuration.

Use PanelBuilder software 4.00.02 or higher.

Ensure that the settings on the KT card match

those entered in the PassĆThrough download

configuration. See the following table for

information on selecting a memory location for

the KT card.

218

FID mismatch detected"

A rack was configured in the PanelBuilder

application that is not an actual PanelView

terminal rack.

Reassign the correct terminal rack using

PanelBuilder software.

221

Unknown external error received from 6200

library"

Screen objects have addresses assigned to the

PassĆThrough block transfer file.

The PLC controller or the PanelView 1200

terminal don't have an 82Ćohm resistor when

running at 230K baud on Remote I/O.
The PassĆThrough block transfer file in the

PanelBuilder application is also being used on a

BTR or BTW instruction in the PLC controller.

Assign a different address to the PassĆThrough

block transfer file, or assign different addresses

to the screen objects.
Install 82Ćohm resistor.

Assign a unique address to the PassĆThrough

block transfer file.

224

Communications board address incorrect"

PanelView 1200 rack assignment is greater than

7.
The KT card bit pattern doesn't match the

jumper setting on the KT card.

Use PanelBuilder software 4.00.02 or higher.

Ensure that the settings on the KT card match

those entered in the PassĆThrough download

configuration. See the following table for

information on selecting a memory location for

the KT card.

For help on solving PanelBuilder software problems, see your
PanelBuilder Development Software User Manual or your PanelBuilder
1200 Configuration Software for Windows User Manual.

PanelBuilder Problems