Б

While trying to download an application file, a

PROBLEM window appears stating: Error code

208 was returned by the PassĆThrough Utility".

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

The PassĆThrough Utility has been unable to

establish DH+ communications with the PLCĆ5.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Б

ББББББББББ

Б

Make sure the Programming Terminal DH+

Address" and the PLC DH+ Address" are

properly assigned.
Make sure that you have selected the proper

DH+ Hardware Driver" for your system, and that

the DH+ Driver Card Location" code is correct.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Immediately after completing a PLCĆ5

PassĆThrough Download, a Minor Fault Status

bit is set in the PLCĆ5.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

The rack assignment configuration of the

application file downloaded to the PanelView

1200 terminal did not exactly match the

application file that was overwritten.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Use the PLCĆ5 6200 Series software to clear the

Minor Fault; then reconfigure the PLCĆ5 to

recognize the new rack assignment.

PLC Controllers Required for PassĆThrough

Important Only specific models and revisions of PLC controllers are
capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.

Processor

Series

Revision

Valid PLC Racks

Baud Rates

PLCĆ5/11

All

All

3 octal

57.6 kbps

115.2 kbps

230.4 kbps

PLCĆ5/15

B

N or later

1-3 octal

57.6 kbps

PLCĆ5/20

All

All

1Ć3 octal

57.6 kbps

115.2 kbps

230.4 kbps

PLCĆ5/25

A

J or later

1-7 octal

57.6 kbps

PLCĆ5/30

A

B or later

1-7 octal

57.6 kbps

115.2 kbps

230.4 kbps

PLCĆ5/40

A

B

E or later

B or later

1-17 octal

57.6 kbps

115.2 kbps

230.4 kbps

PLCĆ5/60

A

B

E or later

B or later

1-27 octal

57.6 kbps

115.2 kbps

230.4 kbps

PLCĆ5/250

All

All

1-37 octal

57.6 kbps

115.2 kbps

230.4 kbps