Rockwell Automation 2090-SRxxx External Shunt Modules Installation Instructions User Manual

Page 10

Advertising
background image

Publication 2090-IN004B-EN-P — June 2008

10 External Shunt Modules

When mounting your shunt module inside the enclosure, follow these
additional guidelines:

Metal-clad modules can be mounted anywhere in the dirty zone,
but as close to the Ultra3000 drive as possible.

Shunt DC-bus wires can be run with motor power cables.

Keep unshielded wiring as short as possible. Keep shunt DC-bus
wiring as flat to the cabinet as possible.

Separate shunt DC-bus cables from other sensitive, low voltage
signal cables.

External Shunt Resistor Mounted Inside the Enclosure

C

C

VD

D

D

VD

D

D

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

Motor

DC Bus

100-240 VAC

50/60 Hz

L1

AUX

L2/N
AUX

L2/N

L1

-

+

W

V

TB1

External

Shunt

3

2

1

Internal

TB2

U

Dirty Wireway

Clean Wireway

Motor Power Cable

Route Motor Power
Shielded Cable

Route Encoder/Analog/Registration

Shielded Cables

Enclosure

24V

Power Supply

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

Ultra3000
(460V) Drive
System

Very dirty power connections

segregated (not in wireway).

Very dirty shunt connections

segregated (not in wireway).

Maximum length is 3.05 m (10 ft).

Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, 2 twists per foot, min (3rd choice).

150 mm (6.0 in.)

clearance, min on all four

sides of the shunt module.