Noise Zones for Ultra3000/Ultra5000 Drives

Observe these guidelines when mounting your external shunt module
outside the enclosure:

Mount circuit components and wiring in the very dirty zone or
in an externally shielded enclosure. Run shunt DC-bus and fan
wiring inside metal conduit to minimize the effects of EMI and
RFI.

Mount resistors (other than metal-clad) in a shielded and
ventilated enclosure outside the cabinet.

Keep unshielded wiring as short as possible. Keep shunt DC-bus
wiring as flat to the cabinet as possible.

External Shunt Resistor Mounted Outside the Enclosure

C

C

VD

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

D

D

VD

D

D

D

Motor

DC Bus

100-240 VAC

50/60 Hz

L1

AUX

L2/N
AUX

L2/N

L1

-

+

W

V

TB1

External

Shunt

3

2

1

Internal

TB2

U

Dirty Wireway

Clean Wireway

Motor Power Cable

Very dirty shunt connections

segregated (not in wireway).

Maximum length is 3.05 m (10 ft).

Route Motor Power
Shielded Cable

Route Encoder/Analog/Registration

Shielded Cables

Customer-supplied

Metal Enclosure

Metal Conduit

(where required by local code)

Enclosure

Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, 2 twists per foot, min (3rd choice).

24V

Power Supply

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

Ultra3000
(460V) Drive
System

Very dirty power connections

segregated (not in wireway).

150 mm (6.0 in.)

clearance, min on all four

sides of the shunt module.