Rockwell Automation 2090-SRxxx External Shunt Modules Installation Instructions User Manual

Page 8

Advertising
background image

Publication 2090-IN004B-EN-P — June 2008

8 External Shunt Modules

When mounting your shunt module inside the enclosure, follow these
additional guidelines:

Metal-clad modules can be mounted anywhere in the dirty zone,
but as close to the Kinetix 6000 system as possible.

Shunt DC-bus wires can be run with motor power cables.

Keep unshielded wiring as short as possible. Keep shunt wiring
as flat to the cabinet as possible.

Separate shunt DC-bus cables from other sensitive, low voltage
signal cables.

External Shunt Module Mounted Inside the Enclosure

C

D

D

D

D

D

VD

C

VD

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

D

Line Interface Module

Kinetix 6000

Drive System

Dirty Wireway

Clean Wireway

Motor Power Cables

Enclosure

2094-BSP2

Shunt Module

I/O and Feedback Cables

150 mm (6.0 in.)

clearance, min on all four

sides of the shunt module.

Shunt Thermal Switch and Fan Wires (when present)

Very Dirty Connections Segregated

(not in wireway)

Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, two twists per foot, min (3rd choice).

No sensitive

equipment within

150 mm (6.0 in.).

Route 24V DC I/O

shielded cable.

Route encoder/analog/registration

shielded cables.