Publication 2090-IN004B-EN-P — June 2008

6 External Shunt Modules

Minimum Clearance Requirements (outside the enclosure)

HF Bonding Your Shunt Module

Bonding is the practice of connecting metal chassis, assemblies,
frames, shields, and enclosures to reduce the effects of
electromagnetic interference (EMI). For more information on the
concept of high-frequency (HF) bonding, the ground plane principle,
and electrical noise reduction, refer to System Design for Control of
Electrical Noise Reference Manual, publication

GMC-RM001

.

Establishing Noise Zones

This table provides the zoning requirements of cables connecting to
the external shunt module.

1394 Digital Servo Controller

3600W Shunt Module

BULLETIN 1394 3600W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

150 mm (6.0 in.) clearance
for airflow and installation.

150 mm (6.0 in.) clearance

for airflow and installation.

150 mm (6.0 in.) clearance

for airflow and installation.

254 mm (10.0 in.) clearance

for airflow and installation.

Bulletin 1394 and 2090
External Shunt Modules

(1394-SR36Ax module is
shown in this example.)

IMPORTANT

To improve the bond between the drive system and subpanel,
construct your subpanel out of zinc plated (paint-free) steel.

Wire/Cable

Zone

Method

Very

Dirty

Dirty

Clean

Ferrite

Sleeve

Shielded

Cable

COL, DC+ (shielded option)

X

X

COL, DC+ (unshielded option)

X

Thermal switch

X

X

Fan (if present)

X