Wire the Thermal Switch

This procedure applies to only the 1394-SR36AF shunt module and
assumes that you have mounted the module, wired the power
connections, and are ready to connect the thermal switch wires.

Refer to

Additional Resources

on

page 22

for the servo drive user

manual with the drive-end installation instructions.

Wire should be copper with 75

°

C (167

°

F) minimum rating.

Thermal Switch Wiring Requirements

Follow these steps to wire the thermal-switch terminal block.

1. Verify that all power is removed from the system.

2. Open the front door of the shunt module.

3. Insert one wire into the top terminal of the thermal-switch

terminal block.

4. Insert the other wire into the lower terminal of the

thermal-switch terminal block.

Refer to the figure on

page 16

for the location of the

thermal-switch terminal block.

5. Tighten all screw terminals.

6. Gently pull on each wire to make sure it does not come out of

its terminal; reinsert and tighten any loose wires.

External Shunt Module

Cat. No.

Thermal
Switch
Connections

Recommended
Wire Size
mm

2

(AWG)

Torque Value
N•m (lb•in)

1394-SR36AF

TS1

0.75 (18)

0.6 (6)

TS2

TS1

TS2