Noise zones for 1394 drives – Rockwell Automation 2090-SRxxx External Shunt Modules Installation Instructions User Manual

Page 11

Advertising
background image

Publication 2090-IN004B-EN-P — June 2008

External Shunt Modules 11

Noise Zones for 1394 Drives

Observe these guidelines when mounting your external shunt module
outside the enclosure:

Mount circuit components and wiring in the very dirty zone or
in an externally shielded enclosure. Run shunt DC-bus and fan
wiring inside metal conduit to minimize the effects of EMI and
RFI.

Mount resistors (other than metal-clad) in a shielded and
ventilated enclosure outside the cabinet.

Keep unshielded wiring as short as possible. Keep shunt DC-bus
wiring as flat to the cabinet as possible.

Route thermal switch and fan wires separate from shunt DC-bus.

External Shunt Module Mounted Outside the Enclosure

C

C

D

D

VD

D

C

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

Status

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

SERCOS System Module

(1)

Dirty Wireway

Clean Wireway

Customer-supplied

Metal Enclosure

Enclosure

Metal Conduit

(where required

by local code)

Route 24V DC I/O

Shielded Cable

Route Encoder/Analog/Registration

Shielded Cable

Very dirty shunt connections

segregated (not in wireway).

24V Motor

Brake PS

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

1394x-SJT22-x Drive System

I/O and

Feedback Cables

Enclosure

Shunt thermal switch and

fan wires (when exist).

Shunt DC-bus Wiring Methods:

Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, 2 twists per foot, min (3rd choice).

150 mm (6.0 in.)

clearance, min on all four

sides of the shunt module.