Interpreting the Status Indicators

The status indicators on the 9220-KTCT give you information about the
card and the network when you’re connected via the BNC connectors.

The table below outlines the states, and explains what each state means
to you and the action you should take, if any, to correct that state.

steady –

indicator is on continuously in the defined state.

alternating –

the two indicators alternate between the two defined states at the same time (applies to

both indicators viewed together). The two indicators are always in opposite states, out of phase.

flashing –

the indicator alternates between the two defined states (applies to each indicator viewed

independent of the other). If both indicators are flashing, they must flash together, in phase.

and

A

B

Cause

Action

off

no power

none or power up

steady red

faulted unit

cycle power or reset unit

If fault persists, contact A-B representative
or distributor.

alternating red/green

self-test

none

alternating red/off

incorrect node configuration

check network address and other
ControlNet configuration parameters

or

A

B

Cause

Action

off

channel disabled

program network for redundant media,
if required

steady green

normal operation

none

flashing green/off

temporary errors

none; unit will self-correct

ree o

node is not configured to go on line

make sure the configuration node is
present and working

À

flashing red/off

media fault

check media for broken cables, loose
connectors, missing terminators, etc.

no other nodes present on network

add other nodes to the network

flashing red/green

incorrect network configuration

cycle power or reset unit

If fault persists, contact A-B representative
or distributor.

À The configuration node is the node responsible for distributing ControlNet configuration data to all nodes on

the network.