DeviceNet to SCANport Communication Module with Digital Inputs Parameters
B-3
Class 1 Drop Cable is available in three spool sizes:
3. Reset the adapter by setting the Reset Adapter (22) parameter to
Enable.
Using Datalinks and Command
I/O
Command I/O provides two 16-bit words of input and two 16-bit
words of output when enabled. Datalinks let you increase the size of
I/O to and from a SCANport
device (provided the SCANport device
supports datalinks). By enabling datalinks, you can continuously
change or monitor the value of a parameter without using the
DeviceNet to SCANport messaging function.
Datalinks consist of two 16-bit words of input and two 16-bit words
of output when enabled. They provide up to eight words (in and out)
of data if they are supported in the connected SCANport product.
Cable Part Number
Spool Size
1485C-P1-B50
50m (164 ft.)
1485C-P1-B150
150m (492 ft.)
1485C-P1-B300
300m (984 ft.)