DeviceNet Objects
C-5
Class Code 0x03 — DeviceNet 
Object
The DeviceNet Object is used to provide the configuration and status 
of a physical attachment to DeviceNet. A product must support one 
(and only one) DeviceNet Object per physical network attachment.
Class Attributes
Instances
Not supported.
Instance Attributes
Common Services
Not supported.
Attribute
ID
Access
Rule
Name
Data
Type
Description
1
Get
DeviceNet 
Specification
Word
Returns 2.
Attribute
ID
Access
Rule
Name
Data
Type
Description
1
Get
Mac ID
USINT
Node Address.
2
Get
Data Rate
USINT
Data Rate.
3
Get
BOI
BOOL
Default = 0.
4
Set
Bus Off 
Counter
USINT
Increments if BOI is non-
zero and Bus Off occurs. 
Can only be set to zero.
5
Get
Allocation 
Information
STRUC
T of
BYTE
USINT
The allocation 
information a slave 
supports when the 
master allocates.
6
Get
Node Adx 
Switch Err
BOOL
If non-zero, the Node 
Address NVS value does 
not match the online 
value.
7
Get
Data Rate 
Switch Err
BOOL
If non-zero, the Data 
Rate NVS value does not 
match the online value.
8
Get
Node Adx 
Switch
USINT
The actual value in the 
EEPROM.
9
Get
Data Rate 
Switch Val
USINT
The actual value in the 
EEPROM or the 
operating value after an 
autobaud was 
completed.