Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 143
 
Publication 2100-UM001B-EN-P – January 2001
DeviceNet to SCANport Communication Module with Digital Inputs Parameters
B-17
DeviceNet to SCANport 
Communication Module with 
Digital Inputs Parameters
The following table provides information on the DeviceNet to 
SCANport Communication Module with Digital Inputs parameter set.
Important:
When accessing this parameter set
through the
DeviceNet Parameter Class, add
the adapter’s parameter number
to
the number of the last parameter of the SCANport device.
When
accessing this parameter set
through the vendor-specific SCANport
Variables-Linear Class, add the adapter’s parameter number to 
4000H.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power
Cycle
Description
1
SCANport
Adapter
0-7
NA
No
No
Identifies the port number to which the adapter 
is connected on the SCANport product.
2
DN Node
Address
0-63
63
Yes
Yes
Identifies the DeviceNet Node Address for the 
adapter.
3
DN Data Rate
125K
250K
500K
Auto
Auto
Yes
Yes
Identifies the data rate used on the DeviceNet 
network.
Important: At least one node on your 
DeviceNet network must be configured to a 
data rate (125, 250, or 500 K), not autobaud.
4
Cmd/Stat Con-
fig
Off, On
On
Yes
Yes
Determines whether to pass logic command and 
analog reference control data from a DeviceNet 
connection to a SCANport product.
5
Datalink A Cfg
Off, On
Off
Yes
Yes
Determines whether to pass control data 
contained in datalink A from a DeviceNet 
connection to the SCANport product.
6
Datalink B Cfg
Off, On
Off
Yes
Yes
Determines whether to pass control data 
contained in datalink B from a DeviceNet 
connection to the SCANport product.
7
Datalink C Cfg
Off, On
Off
Yes
Yes
Determines whether to pass control data 
contained in datalink C from a DeviceNet 
connection to the SCANport product.
8
Datalink D Cfg
Off, On
Off
Yes
Yes
Determines whether to pass control data 
contained in datalink D from a DeviceNet 
connection to the SCANport product.
Important:
For information on accessing and editing parameters, refer to Chapter 3, Configuring the DeviceNet to SCANport
Communication Module with Digital Inputs.