B-24 DeviceNet to SCANport Communication Module with Digital Inputs Parameters
M-S Input Parameter Configurations
The M-S Input (24) parameter has the following five configurable bits.
Figure 5 Bits and Corresponding I/O
When you enable the Cmd/Stat (4) or datalink (5-8) parameter(s) in the adapter, 
you must set the corresponding bit in the M-S Input (24) parameter if you want 
the input data to come from the scanner or master device.
The following table lists possible configurations for the M-S Input (24) 
parameter and the types of allocation associated with each.
xxx0, 0 0 0 0
datalink D
datalink C
datalink B
datalink A
Cmd/Ref
0 = Peer or other input
1 = Master-Slave input
ADAPTER 
CONFIGURATION
ALLOCATION (Number Of Words)
Data Size Sent From The Controller To The Adapter
M-S Input
M-S 
Output
Poll Only
COS Only
Cyclic 
Only
Poll & 
COS
Poll & 
Cyclic
00000
xxxx0
0
NA
NA
NA
NA
00001
xxxx0
2
NA
NA
NA
NA
00010
xxxx0
2
NA
NA
NA
NA
00011
xxxx0
4
NA
NA
NA
NA
00100
xxxx0
2
NA
NA
NA
NA
00101
xxxx0
4
NA
NA
NA
NA
00110
xxxx0
4
NA
NA
NA
NA
00111
xxxx0
6
NA
NA
NA
NA
01000
xxxx0
2
NA
NA
NA
NA
01001
xxxx0
4
NA
NA
NA
NA
01010
xxxx0
4
NA
NA
NA
NA
01011
xxxx0
6
NA
NA
NA
NA
01100
xxxx0
4
NA
NA
NA
NA
01101
xxxx0
6
NA
NA
NA
NA
01110
xxxx0
6
NA
NA
NA
NA