DeviceNet to SCANport Communication Module with Digital Inputs Parameters
Using Fault Configurable 
Inputs
You can select constant values that your adapter will maintain in the 
event of a controller mode change or error. These constant values are 
referred to as Fault Configurable inputs. When the controller is placed 
in program mode or a DeviceNet network fault occurs, the control 
outputs from the adapter to the SCANport product can be set to 
automatically switch to the constant values set in the Fault Cfg In 
parameters. This lets you define a safe operating state for controlled 
devices that depend on pre-programmed output from the adapter.
If you intend to use Fault Configurable inputs, you must do the 
following:
1. Set desired values for the Fault Cfg Logic (11), Fault Cfg Ref
(12), and Fault Cft In (13 – 20) parameters.
2. Set the Idle Fault Config (9) parameter and/or the Comm Flt
Action (10) parameter to Fault Cfg.
Refer to Chapter 3, Configuring the DeviceNet to SCANport 
Communication Module with Digital Inputs, for instructions on 
editing parameters.
!
ATTENTION: Risk of severe bodily injury or 
equipment damage exists. The Idle Flt Action (9) and 
Comm Flt Action (10) parameters allow the user to 
change the default configuration that would allow the 
module and associated drive to continue to operate if 
communication is lost. Precautions should be taken to 
assure that your settings for these parameters and your 
application do not create a hazard of bodily injury or 
equipment damage.