Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 147
 
Publication 2100-UM001B-EN-P – January 2001
DeviceNet to SCANport Communication Module with Digital Inputs Parameters
B-21
26
COS Status
Mask
0 or 1 for each
bit
0
Yes
No
Provides a mask of the Logic Status word to 
define which bits are checked for changes 
during COS allocation.
0 = Off (not checked).
1 = On (checked).
Important: Refer to your SCANport product’s 
documentation for information on its Logic 
Status word.
27
COS Feed-
back Change
0 = disable
0 = dis-
able
Yes
No
Determines how much (+/-) the feedback word 
can change before a message is sent during 
COS operations.
28
COS/Cyc
Interval
N/A
N/A
No
No
Displays the interval used by the controller to 
check for data in the adapter during COS or 
Cyclic allocation.
29
Peer A Input
Off,
Cmd/Ref
DL A Input 
DL B Input
DL C Input 
DL D Input
Off
Yes
No
Determines where the peer A input is sent in the 
SCANport product.
Important: This parameter cannot be changed 
when the Peer Inp Enable (36) parameter is On.
30
Peer B Input
Off
Cmd/Ref
DL A Input 
DL B Input
DL C Input 
DL D Input
Off
Yes
No
Determines where the peer B input is sent in the 
SCANport product. 
Important: This parameter cannot be changed 
when the Peer Inp Enable (36) parameter is On.
31
Peer Cmd
Mask
0 or 1 for each
bit
0
Yes
Yes
Provides a mask for the Logic Status word 
when it is received through peer input. 
0 = Off (input received from Master).
1 = On (input received from Peer).
32
Peer Ref
Adjust
0-200.00%
0
Yes
No
Provides the percentage of the Reference value 
received through peer input that will be applied 
to the SCANport reference value.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power
Cycle
Description
Important:
For information on accessing and editing parameters, refer to Chapter 3, Configuring the DeviceNet to SCANport