Status

AUTO LOAD (O:3/07)

Output is energized two seconds after the field is applied and
remains closed until the field is removed from the motor by a stop
or a fault.

SCP TRIP (O:3/02)

Output is set high when a Squirrel-Cage Protection Fault occurs.
It is reset when the TRIP output goes high after pushing the reset
button. This signal can be used for indication, via a pilot light, or
it can be used as an optional trip output.

MOTOR PULLOUT TRIP (O:3/03)

Output is set high when the power factor lags for longer than the
programmed trip time delay indicating that the motor has pulled
out. It is reset when the TRIP output goes high after pushing the
reset button. This signal can be used for indication, via a pilot
light, or it can be used as an optional trip output.

INCOMPLETE SEQUENCE TRIP (O:3/04)

Output is set high when an Incomplete Start Sequence Fault occurs.
It is reset when the TRIP output goes high. This signal can be used
for indication, via a pilot light, or it can be used as an optional trip
output.

Specifications

General Specifications

Operating Power

Input Line Voltage – 120 Volts AC 50/60 Hz
Input Current – 0-5 Amps.

Temperature and Humidity

Operating

0°C to 40°C (32°F to 104°F)

Temperature

(Maximum Ambient)

Storage

-20°C to 65°C (-4°F to 149°F)

Humidity

5 to 95% (non-condensing)

Maximum Temp.: 35°C (95°F)