Installation

1901-UM020C-EN-P – June 2013

Wiring Guidelines

The SyncPro™ can accept either two- or three-wire control. The
control chosen will determine the configuration of the control
hardware. Consider the following two inputs and single output
when selecting the type of control:

• I:4/00

NOT STOP input

• I:4/01

START input

• O:3/06

RUN output

If using two-wire control, the two inputs (I:4/00 and I:4/01) are
tied together. They are both low in order to stop the SyncPro (refer
to the summary on page 3-6) and both high in order to run the
device. To start the device after a fault, the START input (I:4/01)
must be taken low and then closed again. In this configuration, the
RUN output acts as a run command. Refer to Figure 3.4.

If using three-wire control, the NOT STOP input must be
maintained high in order to run the device. Momentarily opening
this input will cause the SyncPro to stop (refer to the summary on
page 3-6). Momentarily closing the START input will start the
SyncPro (given that all permissives are satisfied). In this
configuration, the RUN output acts as a start command. Refer to
Figure 3.5.

I:4/00 NOT STOP

I:4/01 START

RUN

O:3/06 RUN

CR

ESR

E-STOP

O/L

O:3/01 TRIP

ESR

External

I:4/07 EQUIP.

SHUTDOWN

OFF

Run Control

Circuit

Emergency

Shutdown

Circuit

I:4/00 NOT STOP

I:4/01 START

RUN

O:3/06 RUN

CR

ESR

E-STOP

O/L

O:3/01 TRIP

ESR

External

I:4/07 EQUIP.

SHUTDOWN

OFF

Run Control

Circuit

Emergency

Shutdown

Circuit

Figure 3.4 – Two-Wire Control