Setup and Commissioning

1901-UM020C-EN-P – June 2013

Setup (cont.)

R

F

1 & R

F

2 Resistor Setup (cont.)

Table 4.A – Feedback Resistor Values • Synchronous Field Feedback Board

Useable Voltage Range

R

F

1/R

F

2

Resistance

(K ohm)

Lower Limit

Upper Limit

2.5

60

160

5

120

320

7.5

170

480

10

230

640

12.5

290

800

15

350

950

17.5

400

1100

20

460

1300

Note:

Resistance value is per resistor (two required).

NOTE : Motor induced currents will cause a voltage to be
produced across the synchronous motor starter field discharge
resistor. This voltage is connected to the feedback resistors and
the tap to be selected on these resistors is dependent on this
voltage level. For example, if the discharge resistor value is 20
ohms and the induced currents are 30 amperes at 0 speed and 18
amperes at 95 percent speed, then the induced voltage seen by the
feedback resistors will range from 600 volts (0 speed) to 360 volts
(95% speed). The selection would then be 10 kilohms on each of
the 2 resistors. In the event that the induced voltage proves to be
higher than allowed by the chart, it will be necessary to tap the
field discharge resistor at a point which will allow the value to fall
within the chart. Refer to Rockwell Automation for assistance.