Setup

Check the following components of the SyncPro once it has been
installed.

Lithium Battery

Ensure the supplied lithium battery is connected. This battery
maintains power to the processor, preserving programmed set
points loaded into RAM memory through the DTAM. To verify
the connection, remove the processor in slot 0 of the I/O rack. The
battery is on the printed circuit board with wires extending from it
to a keyed connector. The connector must be plugged into the
matching keyed receptacle.

Analog Card DIP switches

Remove the analog card from slot 1 of the I/O rack and verify that
the DIP switches on the side of the printed circuit board have both
been set to the ‘ON’ position. For further details, refer to the
analog card publication number 1746-NIO4I. These are normally
set at the factory.

Programmer/Display DTAM

Prior to usage the DTAM must be configured as follows while
connected to a functional SyncPro 5/03 with the Synchronous
Protector program. Refer to the DTAM manual 1747-ND013 for
more detailed information on the procedure. This setup procedure has
been performed in the factory, but in case of difficulty, the following
procedure may be used. Ensure the jumper in the back of the DTAM
is connected between pins 1 and 2 to enable the MODIFY mode.

Apply power to the SyncPro controller.

On the DTAM, press the [7] and [INC] keys simultaneously
until the Modify Setup Screen is obtained.

Press [ENTER] (for Confirmation)

Press [ENTER] (for English)

Press the [INC] or [DEC] keys to show the number 2, press
[ENTER] (for DTAM address)

Press the [INC] or [DEC] keys to show 19200, press [ENTER]
(for the Baud Rate)

Press the [INC] key to show ON, press [ENTER] (for auto attach)

Press the [INC] key to show ON, press [ENTER] (for
Backlighting)

Press the [INC] key to show ON, press [ENTER] (for Monitor
Override)

Press [ENTER] (to accept the setup).