Troubleshooting guide – Rockwell Automation 1901 SyncPro User Manual

Page 48

Advertising
background image

7-2

Troubleshooting

1901-UM020C-EN-P – June 2013

Table 7.B – Troubleshooting Guide

Problem or Trip

indicated

Indication of the following conditions

Possible Solutions

Pullout trip (power factor)

[POWER FACTOR TRIP]

• Motor overloaded

• Loss of DC excitation

• Static exciter DC current level set too low

• Lessen the motor loading and/or overload

• Repair static exciter

• Increase current setting on static exciter

Squirrel-cage Protection

Trip

[SQ. CAGE PROT’N]

• Motor overloaded at start

• Remove or lessen load for start

Incomplete Start Sequence

Time Exceeded

[INCOMPLETE START]

• Motor overloaded at start

• Field contactor or FC pilot relay coil failure

• Remove or lessen load for start

• Replace coil(s)

No Transducer Input

[PF–NO XDCR INPUT]

• The transducer is putting out less than 12 mA

when the motor is off (should be 12 mA)

• Check the wiring for the voltage sensing on the

transducer board.

• Replace phase angle transducer board if necessary.

• Replace analog card in SyncPro rack

CT Open/Shorted
[PF–CT OPEN/SHORT]

• The CT is either open or shorted.

• Check the wiring between the CT and the

transducer board.

• Replace the CT if necessary.

CT Reversed

[PF–CT REVERSED]

• The CT is incorrectly wired to the transducer

board.

• Reverse the leads of the CT at the transducer

board.

No Signal @ SLC

[PF–NO SIGNAL@SyncPro]

• There is no signal at the SLC analog card from

the PF transducer board.

• Check the wiring between the transducer board

and the SLC analog card.

• Ensure that there is power to the transducer board.
• Replace the SLC analog card or transducer

board as required.

Transducer Problem

[PF–XDCR PROBLEM]

• The transducer is behaving unpredictably.

• This is an all-encompassing fault and could

include anything from the CT, the transducer board,

or the SLC analog card.

Pulse Board 24 V Failure

[PULSE BOARD 24 V]

• Connection has not been made between the

analog/digital pulse board and the SyncPro DC

input card or from the discharge resistor to the

same A/D pulse board.

• 1746-P2 power supply has had a failure of the 24

V supply.

• Check the connections at the A/D pulse board.

• Check fuse in power supply. Check for 24 V at

power supply. Replace power supply if necessary.

• Replace A/D pulse board.

Field Voltage Loss
[FIELD VOLT LOSS]

• The static exciter is not actively producing DC or

the FVR relay coil has failed.

• Wrong polarity on FVR coil.

• Incorrect voltage rating of FVR coil.

• Exciter Enable (EE) relay did not pick up.

• Service the static exciter or repair the FVR relay.

• Check polarity on FVR coil.

• Check voltage rating of FVR coil.

• Verify the control circuit.

Field Current Loss

[FIELD AMPS LOSS]

• The current relay which monitors the motor field

current is not providing an energized contact to

verify that the static is functional.

• Check both the field current relay and the static

exciter for possible failures.

No Field Coil Feedback

[FIELD CONTACTOR]

• The SyncPro has requested the field contactor to

energize but the feedback contact from this

contactor is not showing as closed.

• The field contactor coil has failed. Replace the coil.

• The connection to the FC auxiliary has not been

made. Check the wiring.

• The FC auxiliary contact has failed. Replace the

contact.

Reversed PF @ SyncPro

[REVERSED PF@SLC]

• The connections from the PF transducer to the

analog card have been accidentally reversed.

• Switch the positive and negative transducer

output leads at the analog card.

External Hardware Fault

[EXTERNAL TRIP]

• An external device to the SyncPro is not

functioning as expected.

• Check external devices.