Chapter 7 - troubleshooting, Last trip table, Troubleshooting – Rockwell Automation 1901 SyncPro User Manual

Page 47: Chapter

Advertising
background image

Chapter

7

Troubleshooting

Last Trip Table

To aid in troubleshooting, the unit stores the last 10 recorded
faults. These can be accessed by viewing the contents of the data
file N22:0, (refer to the DTAM manual 1747-ND013 for
information on data table access). This file forms a circular queue
from N22:1 to N22:10 such that when full, the oldest fault is
discarded making room for the newest.

The value in N22:0 gives the most recent fault. For example:
N22:0 has the value of 6. The most recent fault is found in N22:6,
the one preceding it at N22:5. The fault at N22:10 precedes the
fault at N22:1 in a circular fashion.

The faults are denoted by the following fault codes:

Table 7.A – Last Trip Codes

Fault Code

Description

1

Phase Lag (Pull Out)

2

Squirrel-Cage Protection Trip

4

Incomplete Start Sequence Time Exceeded

8

Power Factor Transducer Ckt

16

Pulse Board 24 V Failure

32

Field Voltage Loss

64

Field Current Loss

128

No Field Coil Feedback

256

Reversed PF @ SyncPro

512

External Hardware Fault

1024

Pulse Board Positive pulse missing

2048

Pulse Board Negative pulse missing

4096

Contactor Feedback

8192

Set Point Data Lost

If more than one fault occurs simultaneously, the value shown
will be the total of the last trip codes. ie. if Field Current Loss
coincided with a Pull Out, the value would be 64+1=65.