Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

Chapter 1 Get Started with the ControlNet Network Fiber Media System

Ring Topology

A ring topology provides redundancy by providing two data paths in a single ring.
A ring can sustain two faults before that data connection is lost. You should
consider a ring when your devices (Controller and I/O) are single port (A only)
and media redundancy is required. Only the 1786-RPFRL and 1786-RPFRXL
repeater modules support ring topologies.

In a ring topology on the ControlNet network, you can use:

• Up to 5 repeaters by using one 1786-RPA/A repeater adapter.
• The 1786-RPA/B repeater adapter allows for a maximum of 20

1786-RPFRL (long distance) or 1786-RPFRL/X (extra long-distance)
ring repeaters.

Figure 4 - Ring Topology

If a ring is broken, the configuration then becomes a linear bus and the number of
repeaters in SERIES depends on where the ring is broken. You will have as many
repeaters as in the original ring.

See

page 29

to determine different topology constraints.

Up to 20 1786-RPFR(X)L
repeaters on a fiber ring.

Fi

be

r

Fib

er

Fiber

Fibe

r

Fiber

Fib

er

Fi

be

r

Node(s)

Node(s)

Node(s)

Node(s)

Node(s)

Node(s)

Node(s)

RPA +
RPFRXL

RPA +
RPFRXL

RPA +
RPFRXL

RPA +
RPFRXL

RPA +
RPFRXL

RPA +
RPFRXL

RPA +
RPFRXL

Coax

Coax

Coax

Coax

Coax

Coax

Coax

Coax Network

Coax Network

Advertising