23

Get Started with the ControlNet Network Fiber Media System Chapter 1

Install Repeaters in a Combination of Series And Parallel

You can install repeaters in a combination of series and parallel connections. For
mixed topologies (series and parallel) the maximum number of repeaters in series
between any two nodes is 20.

• If you configure your network by using repeaters in combination of series

and parallel, you need to count the repeaters in series on the worst-case
path between any two nodes.

• There can be only one path between any two nodes on a ControlNet

network link. Multiple repeater connections between two segments are
not allowed.

Figure 7 - Repeaters in a Combination of Series and Parallel

In this network example, the maximum number of repeaters that a message will
travel through is 5. The path is as follows: Node 1 to Node 4 travels through
repeaters D, F, C, B, A. Repeaters D and E are in parallel, so you must consider
the path of Node 2 to Node 4 through repeaters E, F, C, B, A. This secondary
path is dependant on the fiber and coax lengths of Segment 1 and Segment 2,
including Segment 7.

31509-M

Coax Segment 7

Repeaters D, E and F are
installed in parallel

Repeater D

Coax Segment 1

Coax Segment 2

Coax Segment 3

Repeater E

Repeater F

Node 1

Node 2

Node 3

Repeater A

Repeater B

Repeater C

Coax Segment 4

Coax Segment 6

Node 4

Node 6

Repeaters A, B, and C are installed in series and connected
to the repeaters in parallel on segment 7 via Repeater F