Rockwell Automation 1786-series ControlNet Fiber Media Planning and Installation Guide User Manual
Page 42

42
Rockwell Automation Publication CNET-IN001C-EN-P - October 2011
Chapter 2 Topology and Signal Considerations
Delay 8
Fiber modules; 94 ns + 901 ns
= 0.995 μs
Delay 9
20 m coax cable x 4.17 ns/m
= 0.083 μs
Total delay for Channel A
= 28.57 μs
Calculate and Total the Delays for Channel B
Delay 1
750 m coax cable x 4.17 ns/m
= 3.127 μs
Delay 2
Coax repeater; 901 ns + 100 ns
= 1.001 μs
Delay 3
1000 m coax cable x 4.17 ns/m
= 4.17 μs
Delay 4
Fiber repeater; 901 ns + 153 ns
= 1.054 μs
Delay 5
3200 m fiber cable x 5.01 ns/m
= 16.032 μs
Delay 6
Fiber modules; 153 + 901 ns + 94 ns = 1.148 μs
Delay 7
100 m fiber cable x 5.01 ns/m
= 0.501 μs
Delay 8
Fiber modules; 94 ns + 901 ns
= 0.995 μs
Delay 9
20 m coax cable x 4.17 ns/m
= 0.083 μs
Total delay for Channel B
= 28.11 μs
Skew between channels =
(Delay through A) – (delay through B) = 28.57 μs – 28.11 μs = 0.46 μs
This is a valid network because the calculated skew of 0.46
μ
s is less than the
maximum allowable skew of 1.6
μ
s.