42

Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

Chapter 2 Topology and Signal Considerations

Delay 8

Fiber modules; 94 ns + 901 ns

= 0.995 μs

Delay 9

20 m coax cable x 4.17 ns/m

= 0.083 μs

Total delay for Channel A

= 28.57 μs

Calculate and Total the Delays for Channel B

Delay 1

750 m coax cable x 4.17 ns/m

= 3.127 μs

Delay 2

Coax repeater; 901 ns + 100 ns

= 1.001 μs

Delay 3

1000 m coax cable x 4.17 ns/m

= 4.17 μs

Delay 4

Fiber repeater; 901 ns + 153 ns

= 1.054 μs

Delay 5

3200 m fiber cable x 5.01 ns/m

= 16.032 μs

Delay 6

Fiber modules; 153 + 901 ns + 94 ns = 1.148 μs

Delay 7

100 m fiber cable x 5.01 ns/m

= 0.501 μs

Delay 8

Fiber modules; 94 ns + 901 ns

= 0.995 μs

Delay 9

20 m coax cable x 4.17 ns/m

= 0.083 μs

Total delay for Channel B

= 28.11 μs

Skew between channels =
(Delay through A) – (delay through B) = 28.57 μs – 28.11 μs = 0.46 μs

This is a valid network because the calculated skew of 0.46