22

Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

Chapter 1 Get Started with the ControlNet Network Fiber Media System

Install Repeaters in Parallel

When you install repeaters in parallel, you can install a maximum of 48 repeaters
(the maximum number of taps per 250 m segment).

Figure 6

shows an example of

fiber repeaters being used in parallel.

Figure 6 - Fiber Repeaters in Parallel

Fiber repeaters A and B are in parallel off of coax segment 1. The network
example shows 2 fiber repeaters in series. This is determined by counting the
number of fiber repeaters a message must travel through to get from one node to
another. For example, if a message travels from node 1 to node 2 (B, C) or from
node 1 to node 3 (A,D), it travels through 2 fiber repeaters.

42307

Coax Segment 1

Coax Segment 2

Coax Segment 3

Node 1

Node 2

Node 3

Repeater A

Repeater B

Repeater C

Repeater D

1786-RPA

1786-RPA

1786-RPA

1786-RPA

1786-RPFM

1786-RPFM

1786-RPFM

1786-RPFM

1794-ACNR15

1794-ACNR15

Fiber Cable 1

Fiber Cable 2