Get Started with the ControlNet Network Fiber Media System Chapter 1

Plan the Installation of the
Fiber Media Components

During the planning phase of your network design, create checklists to help you
determine the following components that are needed in an application:

• Number of nodes in your network

• Length of the fiber segments

• Number of fiber connectors and splices in your network

• Calculate the maximum allowable segment length

• Any additional repeaters and coax segments you need

Choose the Fiber Media
System Composition

The fiber repeater consists of the following:

• A 1786-RPA repeater adapter

• Up to two 1786-RPFRL/B (long-distance) or 1786-RPFRXL/B (extra-long

distance) fiber repeater modules

• Up to four 1786-RPFS (short-distance) or 1786-RPFM (medium-distance)

fiber repeater modules

It is allowable to mix these repeater modules on a single repeater adapter.

Refer to

Table 3 on page 14

to determine how many repeater modules you can

connect to one repeater adapter. The number of repeaters and the total cable
length depends on your network topology limits and the repeater modules
you select.

TIP

In a network containing a fiber repeater module, such as a
1786-RPFRL/B or 1786-RPFRXL/B module, you cannot have more
than 98 node addresses assigned.