Topology considerations – Rockwell Automation 1786-series ControlNet Fiber Media Planning and Installation Guide User Manual

Page 29

Advertising
background image

Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

29

Topology and Signal Considerations Chapter 2

For redundancy, you should do the following on each channel:

• Use the same number and types of repeater assemblies (repeater adapters

plus repeater modules)

• Use the same type of cable
• Keep cable lengths similar
• If using redundant media in a linear bus topology, ring topologies are

not supported.

Figure 10 - Redundant Topology

Topology Considerations

For best results, determine the constraints of your topology. For example, a
maximum of 99 nodes are allowed on a network (98 nodes if you are using
ring redundancy).

31420-M

Table 4 - Topology constraints

Constraint

Example

Only one path is allowed between nodes (non-ring
repeater modules only)

See

Figure 7 on page 23

.

In series topology, maximum of 20 repeaters in a series

In ring topology, up to 20 1786-RPFRL/B or 1786-
RPFRXL/B modules per ring

See

Figure 5 on page 21

See

Figure 8 on page 24

Constraint of each coax segment (taps and trunk-cable
sections)

See

Figure 11 on page 30

.

Constraint of each fiber segment application

See

page 31

.

Power loss budget of each fiber segment

See

Table 5 on page 33

.

Maximum propagation delay through the network

See

page 39

.

Advertising