5 - verify your network, Set network parameters, Measure power loss – Rockwell Automation 1786-series ControlNet Fiber Media Planning and Installation Guide User Manual

Page 55: Chapter 5, Verify your network, Set network parameters measure power loss, Chapter

Advertising
background image

Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

55

Chapter

5

Verify Your Network

Set Network Parameters

You can use RSNetWorx for ControlNet software to determine if network
parameters are set up correctly. Based on the system parameters you entered, such
as, NUT, SMAX, UMAX, and worst-case network delay, RSNetWorx software
calculates scheduled messaging for your network.

If your network is not valid, you must adjust your parameters.

For more information, see Getting Results with RSNetWorx for ControlNet,
publication

CNET-GR001

.

Measure Power Loss

After you install short-, medium- or long-distance fiber cable, check your sections
by using an optical power meter to verify that your attenuation is less than or
equal to the maximum allowed by the fiber type. The light source you are using
must match the wavelength of the fiber module in use.

See

Table 9 on page 56

for the wavelengths of each module.

The power loss measurement should match the tables in Chapter 2. If you do not
follow the cable insertion loss recommendations in

Table 5 on page 33

, you can

assume that you will have high-loss cable and high-loss connections.

Topic

Page

Set Network Parameters

55

Measure Power Loss

55

OTDR Measurement

57

Advertising