Rockwell Automation 1786-series ControlNet Fiber Media Planning and Installation Guide User Manual

Page 63

Advertising
background image

Rockwell Automation Publication CNET-IN001C-EN-P - October 2011

63

Install Your Fiber Repeater Modules and Repeater Adapters Appendix A

2.

Use the key supplied with the ferrite to open it.

3.

Twist the wires, but be careful not to damage them.

4.

Form a loop with both wires (+ and -) approximately 100 mm (4 in.) away
from the power supply connector of the 1786-RPA/B module.

5.

Loop the wires through the ferrite.

6.

Close the ferrite.

Be careful not to damage the wires.

7.

Strip approximately 6 mm (0.24 in.) of wire from the end that will connect
to the power supply connector on the 1786-RPA/B module.

8.

Remove the power supply connector from the 1786-RPA/B module.

9.

Install the stripped ends of the wires in the power supply connector on the
1786-RPA/B module.

10.

Reinsert the power supply connector into the 1786-RPA/B module.

Install the Ferrite at the Relay Contact Connector

1.

Use the key to open the remaining ferrite.

2.

Form a loop with both wires (+ and -) approximately 100 mm (4.0 in.)
away from the relay contact connector of the 1786-RPFRL/B or
1786-RPFRXL/B module.

IMPORTANT

Do not use more than one ferrite per 1786-RPA/B module.

Loop the wire
around the ferrite.

Twist the wires.

31530

Connect the power supply wires.

31528

Advertising