9.10.6 Parameter Specifications

9.10.6.1 AB, abort

Purpose:

The AB (abort) control input lets the user application cancel the execution of an
on-going sequence of tests.

Data type:

Boolean

Direction:

From user application to ITSTM
From user application to OTSTM

Values:

TRUE
FALSE
Default: FALSE

Notes:

The AB input is edge triggered. On a rising edge any test in progress is
aborted.

9.10.6.2 AMOA / AMOB, all module outputs A / B

Purpose:

The AMO (all monitors on) inputs to the RMET are used by the test procedure
in the RMET.

Data type:

Boolean

Direction:

From user application to RMET

Values:

TRUE: all the channels on the slice are on
FALSE: one or more channels on the slice are off

Notes:

Connect AMOA and AMOB to the A and B slices of the TM117-RME/SME
monitored output termination module.

9.10.6.3 COUNT, counter

Purpose:

The COUNT outputs from the RMET and DIPT are records of the quantity of
completed tests done by their function blocks. COUNT is set to zero on a RST
(reset) command.

Data type:

analogue

Direction:

From RMET to user application
From DIPT to user application

Values:

0 to 65,535

Notes:

The COUNT outputs are confidence outputs. The application can examine
them to make sure that tests are actually being done.

9.10.6.4 CMD, command

Purpose:

The CMD input to the RMET represents the commanded output states from the
application. It is not for direct use by the user application.

Data type:

analogue

Direction:

From PACK16 to RMET

Values:

0 to 65,535 (bit-packed integer)

9.10.6.5 DIC, digital input configuration

Purpose:

The DIC control input lets the user application configure the ITSTM to work with
simplex and duplex digital input modules

Data type:

Boolean

Direction:

From application to ITSTM

Values:

TRUE - dual DI module
FALSE - single DI module

Notes:

The application must set DIC to the applicable value

9.10.6.6 DIM, digital input mode

Purpose:

The DIM (digital input mode) is an encoded output from the ITSTM to each
DIPT. It is not for direct use by the user application.

Data type:

analogue

Advertising