SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 96 of 103

9.10.6.13 IPV, input verification

Purpose:

The IPV (input verification) output represents the field input of the channel.

Data type:

Boolean

Direction:

From DIPT to application

Values:

TRUE – input channel (voted) high
FALSE – input channel (voted) low

Notes:

IPV is the voted input state to be used by the application.

9.10.6.14 LF, line fault

Purpose:

The LF (line fault) output is a logical OR of the SC and OC outputs from the
LFLT

Data type:

Boolean

Direction:

From LFLT to application

Values:

TRUE - either SC or OC (or both) is TRUE
FALSE – SC and OC are FALSE

9.10.6.15 MDA / MDB, monitor discrepancy

Purpose:

The MDA and MDB (monitor discrepancy) parameters show when there is a
discrepancy.

Data type:

Boolean

Direction:

From application to RMET

Values:

FALSE – a discrepancy exists between the commanded and actual states of
one of more output channels in a TM117-RME/SME termination module
Otherwise TRUE

Notes:

Connect MDA and MDB to the A and B slices of the TM117-RME/SME
monitored output termination assembly.

9.10.6.16 MTS, manual test start

Purpose:

The MTS (manual test start) input starts a test sequence if there is no test
already in progress.

Data type:

Boolean

Direction:

From application to ITSTM or OTSTM

Values:

TRUE
FALSE

Notes:

Make sure that the application returns MTS to FALSE promptly. This input
parameter is level sensitive, and will cause repetitive testing (and relay chatter)
if it is held TRUE.

9.10.6.17 OC, open circuit

Purpose:

The OC (open circuit) output tells the application when the value of the process
input is less than the OCTHR

Data type:

Boolean

Direction:

From LFLT to application

Values:

TRUE – the process input is less than the OCTHR
Otherwise FALSE

9.10.6.18 OCTHR, open circuit threshold

Purpose:

The OCTHR (open circuit threshold) determines the low (or open circuit)
threshold for the analogue input tested by the LFLT

Data type:

analogue

Direction:

From application to LFLT

Values:

41 to 4,054

9.10.6.19 OPA / OPB, output A / B

Purpose:

The OPA and OPB outputs control each of two TM117-RME/SME monitored
output termination module output slices. OPA and OPB are not for direct use by